Calculate the estimated resistance of a single vertical earth rod using soil resistivity, rod length and rod diameter. This calculator uses a standard engineering formula for preliminary earthing design.

Earth Rod Resistance Calculator

Calculate the estimated resistance of a single vertical earth electrode using soil resistivity, rod length and rod diameter.

Unit: Ω·m
Unit: metres (m)
Unit: millimetres (mm)
Estimated Earth Rod Resistance
—
Engineering Formula
R = ρ / (2πL) × [ln(4L/d) − 1]

Where:
ρ = Soil resistivity (Ω·m)
L = Earth rod length (m)
d = Earth rod diameter (m)
Engineering Note: This calculator provides an estimated resistance for a single vertical earth electrode assuming relatively uniform soil conditions. Actual field resistance may vary due to soil stratification, moisture, temperature, electrode installation and surrounding conditions. For final project design, field soil resistivity measurements and applicable engineering standards should be considered.