Soil Resistivity Measurement – Wenner Four-Point Method

The Wenner four-point method uses four equally spaced electrodes to measure soil resistivity. The outer electrodes (C1 and C2) inject current, while the inner electrodes (P1 and P2) measure the potential difference.

Wenner four-point soil resistivity test setup showing C1, P1, P2 and C2 electrodes with equal spacing a
Figure: Wenner four-point electrode arrangement. Electrode spacing between adjacent probes is a.
Measurement principle

For the standard Wenner method, soil resistivity is calculated as ρ = 2πaR, where a is the equal spacing between adjacent electrodes in metres and R is the measured resistance in ohms. The result is expressed in Ω·m.

Calculated Soil Resistivity
62.83 Ω·m
Electrode spacing: 1 m | Measured resistance: 10 Ω

Engineering Formula

Wenner 4-point method:

ρ = 2πaR

Where:

ρ = Apparent soil resistivity (Ω·m)

a = Equal spacing between adjacent electrodes (m)

R = Measured resistance from the instrument (Ω)

Engineering Note

This formula assumes equal spacing between four electrodes and electrode depth small compared with the spacing. The result is apparent soil resistivity for the selected test spacing, not necessarily the true resistivity of every soil layer. For accurate field testing, follow the instrument manufacturer’s procedure and the applicable test standard. Multiple spacings may be needed to assess soil layering.