Engineering Formula
Simplified preliminary grid resistance estimate:
Rg ≈ ρ [1/LT + 1/√(20A) × (1 + 1/(1 + h√(20/A)))]
ρ = Soil resistivity (Ω·m)
LT = Estimated total electrode length (m)
A = Grid area (m²)
h = Assumed burial depth (m)
The estimate uses the entered grid dimensions and spacing to estimate the horizontal conductor length, then adds the entered vertical rod lengths. This simplified model does not rigorously calculate rod mutual effects or all grid geometry factors.
This tool is for preliminary estimation only. It assumes uniform soil resistivity and an assumed burial depth of 0.5 m. Actual grounding resistance depends on soil layering, electrode geometry, conductor arrangement, rod interactions and field conditions. This tool does not calculate ground potential rise, step voltage, touch voltage, fault-current division or conductor thermal sizing. Do not use this result alone for personnel-safety decisions or to claim IEEE 80 compliance. Final design requires appropriate engineering analysis and field verification.