Earthing Backfill Compound Quantity Calculator

Calculate BFC quantity, number of bags and mixing water for earthing installations.

1. Select Installation Type

Earth Rod Borehole Dimensions

Enter 0 if rod volume should not be deducted.

2. Quantity Settings

For overbreak, losses or extra filling; enter 0–50%.

3. BFC Yield and Water Mixing

Set these values for your product. Wet-mix yield determines how much dry BFC is required to fill the available space. The water ratio determines the mixing water separately. Both values are editable.
Illustrative default: 1 L/kg. Replace with measured product yield.
Default: 3 kg BFC per 1 L water. Change for a custom ratio.

How It Is Calculated

Available space: installation volume minus the volume occupied by rods or conductors.

Target wet-fill volume: available space × number of installations × (1 + allowance ÷ 100).

Dry BFC required: target wet-fill volume in litres ÷ wet-mix yield in litres per kg.

Water required: dry BFC required in kg ÷ kg of dry BFC per litre of water.

Bags to purchase: round up (dry BFC required ÷ selected bag size).

Important: The default yield of 1 L/kg and water ratio of 1 L per 3 kg are illustrative and editable, not universal product specifications. Confirm both using your BFC formulation and mixing trials. The calculator targets the entered installation volume; actual installed yield may vary with mixing, compaction, voids and site conditions.