Estimated Minimum Conductor Area
— mm²
Preliminary thermal sizing estimate

Engineering Formula

Adiabatic short-circuit equation:

S = I√t / k

S = Minimum conductor cross-sectional area (mm²)

I = Fault current (A)

t = Fault clearing time (s)

k = Material and temperature-dependent constant

This calculator uses the selected k value directly. The displayed initial and final temperatures are checked for validity but do not automatically recalculate k.

Engineering Note

This is a preliminary thermal sizing estimate only. The k value must be appropriate for the conductor material, conductor construction, insulation or surface condition, and specified initial and final temperatures under the applicable standard. The illustrative steel value is not universal. Final sizing must also consider mechanical strength, corrosion, installation, fault-current division, protection clearing time and applicable project standards. This calculator does not establish IEEE 80 compliance or personnel safety.