Engineering Calculation
Building perimeter:
P = 2 × (Length + Width)
Preliminary down-conductor quantity:
N ≈ ⌈P / selected spacing⌉
Rolling-sphere reference radii:
Class I: 20 m | Class II: 30 m
Class III: 45 m | Class IV: 60 m
This calculator provides a preliminary perimeter-based estimate only. The selected down-conductor spacing is a user input, not an automatically verified IEC 62305 requirement. Actual quantity and locations depend on the applicable standard edition, building geometry, roof layout, natural components, separation distances, bonding, earth termination design and project-specific risk assessment. Rolling-sphere radius alone does not determine the number or placement of air terminals. Final design must be verified by a qualified lightning protection designer.