Calculate the estimated resistance of multiple interconnected vertical earth rods considering soil resistivity, rod dimensions, number of rods and rod spacing.
Engineering Formula
Single rod:
R₁ = ρ / (2πL) × [ln(4L/d) − 1]
Mutual resistance between two rods:
Rₘ = ρ / (2πL) × ln[√((L/s)² + 1 + L/s)]
The calculator considers the mutual resistance between equally spaced rods arranged in a straight line.
This calculator provides an estimated resistance for equally spaced vertical earth rods arranged in a straight line. Actual earthing resistance may vary depending on soil stratification, electrode installation conditions, conductor resistance and mutual interference. Field measurement is recommended for final verification.